Pump Overrun on a Boiler: Normal Run-On or a Fault?

Quick answer

Pump overrun is the short period when the boiler's pump keeps running after the burner goes out, moving leftover heat out of the heat exchanger so it does not overheat. A few minutes is normal; Vaillant's ecoTEC plus, for example, defaults to 5 minutes. It points to a fault only when the pump runs on for far longer, runs all the time or the boiler cuts out hot.

On this page
  1. What pump overrun is and why boilers do it
  2. How long pump overrun should last
  3. Fan post-purge: why the fan keeps running too
  4. Is a pump overrun message on the display a fault?
  5. Why overrun goes on too long
  6. Checks you can safely make
  7. When to call a Gas Safe registered engineer

Pump overrun is normal. When your boiler stops firing, the pump, and often the fan, carries on for a few minutes on purpose, carrying leftover heat out of the boiler and into the radiators. It only becomes a problem when it lasts much longer than usual, never stops, or the boiler shuts down on overheat.

What pump overrun is and why boilers do it

When a gas boiler stops firing, its heat exchanger is still very hot. If the pump stopped with the burner, the water inside would sit still and keep absorbing that heat, which can cause boiling in the heat exchanger (the rumbling called kettling), wear on seals and sensors, or an overheat lockout. Running the pump on briefly pushes the heat out to the radiators or cylinder.

Most modern combi and system boilers control this from their own circuit board. On some heat only boilers with the pump outside the casing, the installer gives the boiler a permanent supply so it can keep the pump running after the controls switch off. That wiring is not something to alter yourself.

How long pump overrun should last

Overrun is measured in minutes. Vaillant's installation and maintenance instructions for the ecoTEC plus (document 0020239015_05, page 29) list it as setting d.01, "pump overrun in heating mode", with a factory default of 5 minutes and an installer-adjustable range of 1 to 60 minutes. A second setting, d.18, chooses whether the pump runs continuously (comfort) or intermittently (eco) during heating.

So similar boilers can behave differently, and a pump humming for a few minutes after the heating clicks off is nothing to worry about. As a rough guide:

What you noticeLikely meaning
Pump or fan runs for a few minutes after the burner stopsNormal overrun
Pump runs briefly once a day, even in summerA daily self-check run, also normal
Pump runs in very cold weather with the heating offProbably frost protection
Pump runs for long periods every time, or never stopsExcessive overrun, worth investigating
Boiler cuts out hot, with radiators cold or zones shutPoor circulation, needs an engineer's check

Fan post-purge: why the fan keeps running too

Sometimes it is the fan you hear. Condensing boilers commonly run the fan briefly after the flame goes out, called fan overrun or post-purge, to push remaining combustion gases out through the flue before the next start. Vaillant's ecoTEC plus instructions show this as a status, not a fault: S.06 for fan overrun in heating mode and S.26 in hot water mode, with S.05 covering pump and fan overrun together (page 32). With a basic three-wire controller, the same document says the fan also runs for 20 seconds at each start.

A post-purge is short. A fan that seems to run constantly, or roars without the burner ever lighting, is a fault for an engineer rather than overrun.

Is a pump overrun message on the display a fault?

Not on its own. Many displays show what the boiler is doing, and overrun is one of those states. On a Vaillant ecoTEC plus it appears as status S.07, heating pump overrun; Vaillant faults begin with F.

The Ideal user guides we checked, for the Logic Combi2 and the Logic Max Combi, list faults as codes beginning with F or L or as named fault messages, and pump overrun is not among them. So if an Ideal display mentions the pump or overrun without a fault code, it is reporting normal operation rather than a lockout.

A simple test: overrun ends by itself and the boiler restarts normally on the next demand. A genuine fault stays on the display until it is reset or repaired.

Why overrun goes on too long

The pump keeps going until the boiler sees its temperature fall far enough. Anything that stops water moving freely traps the heat and keeps the pump on.

  • Sludge. Magnetite narrows pipes and radiators; radiators cold at the bottom are a clue. An engineer may suggest a chemical flush (typically £150 to £350) or a powerflush (typically £400 to £800), compared in our powerflush cost guide.
  • Every route closed. All TRVs shut and no bypass leaves the pump nowhere to push water.
  • A sticking or weak pump that runs but moves little water.
  • Zone or diverter valve faults, with a valve stuck part open or closed.
  • Wiring or controls, such as a wiring error or a thermostat still calling for heat.
  • Sensor or PCB faults, where a sensor reads too high or the control board keeps the pump on.

Y-plan, S-plan and the bypass

Cylinder systems use motorised valves: one three-port valve on a Y-plan, two or more two-port valves on an S-plan. When every valve and TRV closes, the overrun water still needs a path, which is the job of an automatic bypass valve or a radiator with no TRV left permanently open. Vaillant's ecoTEC plus instructions call for a bypass at least 1.5 m from the boiler (page 10). Without one, long overrun and overheat lockouts are likely.

Pump running when the heating is off

A short run after the heating switches off is overrun. A brief daily run is a self-check: Ideal's Logic Combi2 user guide (UIN 236183 A01) and Logic Max Combi user guide (UIN 219008 A02) both say the pump runs briefly once every 24 hours regardless of demand. Frost protection can also start the boiler in cold weather. Hours of running with heating and hot water both off points to a valve, wiring, sensor or PCB fault.

Checks you can safely make

  1. Read the pressure gauge with the system cold. It should normally sit between 1 and 1.5 bar. Top up through the filling loop if it is low.
  2. Open at least one radiator fully. Turn a TRV to its highest setting, ideally in a room without a room thermostat, so water always has a route.
  3. Bleed any radiators that are cold at the top. Our guide on how to bleed a radiator covers it step by step.
  4. Check the room thermostat, programmer and any heating app really are off or satisfied, and not still calling for heat.
  5. Time how long the pump runs and note when it happens. A rough log saves an engineer time.

Do not switch off the power at the spur to stop the pump overrunning. Overrun protects the heat exchanger, and cutting the supply while the boiler is hot can make it overheat. Leave the boiler powered, let it finish, and book an engineer if it never stops.

When to call a Gas Safe registered engineer

Book an engineer if the pump runs on for long periods every time, the boiler locks out on overheat, or you hear kettling. They can check the bypass, test the pump and motorised valves, and find out whether a sensor or the control board is at fault. Testing the pump circuit board, an overrun thermostat or the PCB means working inside the casing, so it is strictly their job. Our boiler pump guide explains how the pump itself works, and if the boiler also shuts down mid-cycle, see our guide to a boiler that keeps turning off.

Likely repairTypical UK cost
Engineer call-out and diagnosisTypically £60 to £150
Pump replacementTypically £150 to £400
Motorised or zone valveTypically £180 to £300
Temperature sensor (NTC thermistor)Typically £100 to £200
PCB replacement, fittedTypically £250 to £550

Does it mean I need a new boiler?

Usually not. Excessive overrun is most often a circulation, valve, pump or control fault, and all of those can be repaired. A replacement is only worth discussing if the engineer finds serious wear elsewhere as well, such as a failing heat exchanger on an older boiler.

Frequently asked questions

What does pump overrun mean on a boiler?

It means the pump keeps running for a short time after the burner stops, to carry leftover heat out of the heat exchanger. It is a normal, deliberate function, not a fault.

How long does boiler pump overrun last?

Usually a few minutes. Vaillant's ecoTEC plus installation instructions give a factory setting of 5 minutes for heating pump overrun, adjustable by an installer from 1 to 60 minutes.

What does pump overrun mean on an Ideal boiler?

The same as on any boiler: the pump is running on to clear residual heat. The Ideal Logic user guides we checked list faults as F or L codes or named fault messages, so a pump overrun state without one of those is normal operation.

Why does my boiler pump keep running after the heating goes off?

A few minutes of run-on is overrun, and a brief daily run can be a self-check or frost protection. If it runs for hours, check that at least one radiator is fully open and the pressure is right, then book a Gas Safe registered engineer to check the bypass, valves, sensors and controls.

Do Vaillant boilers need pump overrun?

Yes. Vaillant's ecoTEC plus instructions include a heating pump overrun setting (d.01, default 5 minutes) and require a bypass at least 1.5 m from the boiler so the water has somewhere to go.

How do I fix pump overrun that never stops?

Open one radiator fully, bleed any cold radiators and check the pressure, but never cut the power to stop it. If it still runs on, the cause is usually a missing bypass, a valve, the pump or a sensor, which a Gas Safe registered engineer needs to diagnose.

Sources

How the prices on this page were put together: typical UK prices for the parts and labour involved, shown as ranges rather than quotes. In October 2026 we compared them with the published UK price guides from Checkatrade, MyBuilder, MyJobQuote and Fantastic Services. Prices vary by area, boiler model and engineer, so always ask for a written quote.