What E43 means
E43 is a flame supervision fault: the boiler did light, but the flame signal dropped out again and again while it was running. In the error tables we read, code 43 sits under "loss of flame rectification" and is described as a repeated loss of flame signal during operation. Flame rectification is the small electrical signal the sensing electrode picks up through the flame. When that signal disappears, the boiler has to assume the flame has gone out and shuts the gas off.
The entry appears in Alpha's E-Tec 28 and 33 installation and servicing instructions and in the InTec2 26CE, 30CE and 35CE installation and servicing instructions. In both copies we read, the table columns are not cleanly separated, so the meaning was matched to the code by row order. The two manuals agree, which gives us reasonable confidence, but if your engineer's documentation says otherwise, go with that.
E43 compared with E38 and E01
Alpha uses three related codes, and knowing which one you saw helps:
| Code | What happens | What the boiler does |
|---|---|---|
| E01 | No flame detected during the ignition sequence | Locks out before it has lit |
| E38 | Flame detected, then the signal is lost | Purges with the fan and tries to light again |
| E43 | Flame signal lost repeatedly while running | Stops and shows the fault |
So E43 is effectively E38 happening too often. The manuals tell engineers to check E43 the same way as E38, and they mention that the fault history in the INFO menu can show the related entry as E38.
Causes listed in the Alpha manuals
The checks Alpha gives for this flame loss are:
- The flame sensing electrode and its lead
- Flue gas recirculation, where exhaust gases are drawn back into the air intake
- The gas valve
- The flue system and the terminal outside
- Gas supply and working pressure
- The combustion settings
- The burner earth (listed in the E-Tec 28 and 33 manual)
How the causes tend to differ
These causes fall into three groups. The first is the flame sensing circuit itself: the electrode, its lead and the burner earth. If any of these is worn, dirty or poorly connected, the flame can be burning normally while the boiler reads a weak or broken signal, and the fault can appear at any time regardless of the weather. The second group is the gas side: the supply and working pressure reaching the boiler, the gas valve and the combustion settings. A flame that is unstable because of low working pressure or incorrect settings gives a poor signal, and only an engineer with the right test equipment can measure either. The third group is the flue: the route, the terminal outside and any recirculation of exhaust. Flue problems are the ones most likely to come and go with wind direction and strength.
The high wind note
Alongside these loss-of-flame entries, both manuals carry a note that the fault can occur when the flue is exposed to high wind. Strong gusts across or into the flue terminal can disturb the air and exhaust flow enough to upset the flame. If your E43 only appears on stormy days, that pattern is worth reporting, because it points the engineer towards the flue position and termination rather than a failing part.
What you can safely do
- Check that another gas appliance, such as the hob, lights and burns steadily. If it does not, or your prepayment meter is out of credit, the supply is the problem.
- Check the gas isolation valve under the boiler is fully open, with the handle in line with the pipe.
- Note the weather when the fault appeared, and whether it happened during heating, hot water or both.
- Press reset once. If E43 comes back, stop there and book an engineer.
Do not touch, cover or try to shield the flue terminal, and do not remove the casing to look at the electrode or burner. Flue changes, electrode replacement, gas valve work and combustion checks are all for a Gas Safe registered engineer. If you smell gas, call the National Gas Emergency Service on 0800 111 999.
Our guide to boiler flues gives useful background on how the flue works if wind or recirculation turns out to be the cause.
What the engineer will test
Expect the engineer to read the fault history in the INFO menu, inspect and test the sensing electrode and lead, and measure the gas working pressure at the boiler. They will usually run a combustion check with a flue gas analyser to confirm the settings, and check the flue route and terminal for damage, blockage or a position where exhaust can be drawn back in. If those are all fine, the gas valve and the burner earth come next.
Typical repair costs in the UK
| Job | Typical UK cost |
|---|---|
| Engineer call-out and diagnosis | Typically £60 to £150 |
| Sensing electrode replacement | Typically £90 to £180 |
| Sensing lead or earth connection repair | Typically £100 to £180 |
| Flue repair or adjustment | Typically £150 to £400 |
| Gas valve replacement | Typically £180 to £350 |
Information that speeds up the repair
Tell the engineer your exact model (E-Tec or InTec2, and its size), that the code was E43, how often it happens and whether it lines up with windy weather. Say where the flue comes out, for example through a side wall facing open ground, and whether anything near it has changed, such as a new fence, extension or plant growth. If the boiler also shows E01 or E38 at times, mention that as well.