Baxi E20 Fault Code: Central Heating Sensor Fault

Quick answer

E20 on a Baxi boiler is a "Central Heating NTC Fault": the boiler has lost a usable reading from the temperature sensor on its heating circuit, so it has stopped firing. Baxi treats it as a faulty component, so after checking the power and trying one reset you will need a Gas Safe registered engineer.

On this page
  1. What E20 means on a Baxi boiler
  2. Baxi boilers that use E20
  3. What usually causes E20
  4. What you can safely check
  5. What the engineer will test
  6. Typical repair costs in the UK
  7. E20 and the other Baxi sensor codes

What E20 means on a Baxi boiler

E20 tells you the boiler no longer trusts its central heating temperature sensor, so it has shut the burner down rather than heat water it cannot measure. In practice this is a sensor or connection fault, and the usual fix is a sensor replacement or a wiring repair by a Gas Safe registered engineer.

Baxi's fault tables word it as a "Central Heating NTC Fault". NTC stands for negative temperature coefficient. The sensor is a thermistor, a small component whose electrical resistance falls as it gets warmer. The control board reads that resistance to work out how hot the water leaving the boiler is, then uses the figure to control the burner and protect the heat exchanger. If the reading is missing or makes no sense, the board cannot run the boiler safely.

The Megaflo System HE IE installation manual (UK Comp No 5129838) puts it plainly: "E20 and E28 indicate faulty components". That separates E20 from codes such as E119 or E133, where an outside cause like low pressure or a gas supply problem is common.

Baxi boilers that use E20

Boiler rangeDocumentHow the code appears
Duo-tec Combi 24, 28, 33 and 40 HE AInstallation and Servicing Instructions, UK Comp No 5122323, p.52E, then 20
Duo-tec 2 Combi 24, 28, 33 and 40 GAInstallation and Servicing Instructions 7206334-08, error code table p.45Listed as E20
Assure Combi 25, 30 and 36 (and LPG)Assure Combi User Guide, Table 920, with a symbol beside it
Megaflo System 15 to 32 HE IEInstallation and Servicing Instructions, UK Comp No 5129838, section 18.2E, then 20

The Potterton Gold Combi user guide uses the identical wording for E20, which is no surprise as Potterton is part of Baxi Heating UK. You can find the other Potterton codes we cover from our Baxi fault code hub and the Potterton section.

On the two-character displays, a two-digit code shows as E and then the number, so E20 appears as "E" followed by "20". If you see "E1" followed by two more digits instead, that is a different, three-digit code, which our guide to reading Baxi E1 explains.

What newer Baxi boilers show instead

The 200, 400, 600 and 800 Combi 2 ranges do not use E20. On these boilers the Combi 2/2.1 installation and service manual (7875578-02) lists E.04.01, "Flow temperature sensor short circuited", and E.04.02, "Flow temperature sensor disconnected". They describe the same part failing in two specific ways.

What usually causes E20

  • A failed sensor. This is what Baxi's "faulty component" wording points to. Thermistors can fail open or short after years of heating and cooling.
  • A poor connection. For its flow sensor codes, the Combi 2/2.1 manual tells engineers to check the connection between the sensor and the PCB. A loose plug or corroded terminal gives the board the same nonsense reading as a dead sensor.
  • Damaged wiring. A chafed or broken lead between the sensor and the board has the same effect.

All three sit inside the casing, on or near the heating flow pipe, so none of them is a homeowner job.

What you can safely check

  1. Read the code carefully. Make sure it is E then 20, not part of a longer code.
  2. Check the power. Confirm the fused spur that feeds the boiler is switched on and that the display is lit steadily.
  3. Note the pressure gauge. E20 is not a pressure code, but the reading helps the engineer. The Assure user guide gives a normal range of 1 to 2 bar.
  4. Try one reset. On a Duo-tec, turn the selector to the Reset position and hold it for 5 seconds. On an Assure, press Reset for about one second; the guide warns that holding it for more than two seconds will not reset the boiler. If E20 returns straight away, the sensor circuit is still faulty and further resets will not help.
  5. Look underneath. Check for drips from the boiler or its pipes without opening anything, and mention any you see.

Do not remove the casing to look at the sensor. It sits next to hot pipework and mains-voltage parts, and only a Gas Safe registered engineer should work inside a gas boiler.

What the engineer will test

The fault-finding chart in the Duo-tec Combi HE A manual gives the engineer a reference figure: the CH sensor's cold resistance should be "approximately 10kΩ @ 25° C", and the resistance falls as the temperature rises. The engineer will isolate the boiler, measure the sensor with a meter and compare the reading with that figure. If the sensor is within range, they move on to the plug, the terminals and the lead back to the board.

A replacement sensor is a small part, and once it is fitted the engineer should run the heating and confirm that the boiler reads a sensible flow temperature and modulates normally.

Typical repair costs in the UK

JobTypical cost
Engineer call-out and diagnosisTypically £60 to £150
Central heating temperature sensor (NTC thermistor) replacedTypically £100 to £200
Sensor plug, terminal or wiring repairTypically £100 to £180

If the boiler is still under its Baxi warranty, contact Baxi before booking anyone else, as work by a different engineer can affect a claim.

E20 and the other Baxi sensor codes

Baxi uses a small family of NTC codes, and knowing which one you have tells the engineer which part to bring. E20 covers the central heating sensor. E28 is the flue sensor and E50 is the hot water sensor on older combis, while the Assure adds 40 for the central heating return sensor. If your boiler shows more than one of these together, say so when you book, as a shared wiring or board problem becomes more likely than two sensors failing at once.

Frequently asked questions

Can I clear Baxi E20 by resetting the boiler?

One reset is worth trying, but Baxi lists E20 as a faulty component, so it usually comes straight back. If it does, book a Gas Safe registered engineer rather than resetting again.

Is a Baxi E20 fault dangerous?

The code means the boiler has stopped itself because it cannot read the heating temperature, which is a safe response. Leave it switched off at the fault and have the sensor checked.

Does a Baxi Assure show E20 or just 20?

The Assure Combi user guide lists the fault as code 20, "Central heating NTC fault", shown with a symbol rather than the letter E.

Is Baxi E20 the same as E.04.02 on a Combi 2 boiler?

They involve the same kind of part. On the 400, 600 and 800 Combi 2 ranges, E.04.01 and E.04.02 mean the flow temperature sensor is short circuited or disconnected, which older Baxi boilers report as E20.

Sources

The meaning of E20 on this page comes from these manufacturer documents:

  • Baxi, Duo-tec Combi 24, 28, 33 and 40 HE A: installation and servicing instructions, document Comp No 5122323, Iss 12, 2012.
  • Baxi, Duo-tec 2 Combi 24, 28, 33 and 40 GA: installation and servicing instructions, document 7206334-08, 2013.
  • Baxi, Assure Combi 25, 30 and 36: user guide.
  • Baxi, Megaflo System 15 to 32 HE IE: installation and servicing instructions, document Comp No 5129838, Iss 9, 2012.

Codes and their meanings can change between models and software versions, so the manual for your exact boiler always comes first. Documents with a link open on the manufacturer's own website.

How the prices on this page were put together: typical UK prices for the parts and labour involved, shown as ranges rather than quotes. In October 2026 we compared them with the published UK price guides from Checkatrade, MyBuilder, MyJobQuote and Fantastic Services. Prices vary by area, boiler model and engineer, so always ask for a written quote.